Solis 25KW Three Phase String Inverter

Solis 25KW Three Phase String Inverter

$ 0.00 $ 0.00

Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days

Internal Reference: S5-GC25K

The Solis S5-GC25K is a 25kW three-phase string inverter with a flexible configuration and whisper-quiet operation. It offers IP66 protection, 98.7% max. efficiency, 3/4 MPPT design for multi-facing roofs, intelligent string monitoring with smart I-V curve scan, AFCI protection and 24-hour load consumption monitoring.

Technical Specifications

Models25K30K33K36K40K40K-HV50K-HV
Input DC
Recommended max. PV power37.5 kW45 kW49.5 kW54 kW60 kW60 kW75 kW
Max. input voltage1100 V
Rated voltage600 V
Start-up voltage180 V
MPPT voltage range200-1000 V
Max. input current32 A / 32 A / 32 A4*32 A
Max. short circuit current40 A / 40 A / 40 A4*40 A
MPPT number/Max. input strings number3/64/8
Output AC
Rated output power25 kW30 kW33 kW36 kW40 kW40 kW50 kW
Max. apparent output power27.5 kVA33 kVA36.3 kVA39.6 kVA44 kVA44 kVA55 kVA
Max. output power27.5 kW33 kW36.3 kW39.6 kW44 kW44 kW55 kW
Rated grid voltage3/N/PE, 220 V / 380 V, 230 V / 400 V3/PE, 480 V
Rated grid frequency50 Hz / 60 Hz
Rated grid output current38.0 A / 36.1 A45.6 A / 43.3 A50.1 A / 47.6 A54.7 A / 52.0 A60.8 A / 57.7 A48.1 A60.1 A
Max. output current41.8 A50.2 A55.1 A60.2 A66.9 A53.0 A66.2 A
Power factor>0.99 (0.8 leading - 0.8 lagging)
THDi<3%
Efficiency
Max. efficiency98.5%98.6%98.7%98.8%
EU efficiency98.1%98.2%98.3%98.4%
Protection
DC reverse-polarity protectionYes
Short circuit protectionYes
Output over current protectionYes
Surge protectionDC Type II / AC Type II
Grid monitoringYes
Anti-islanding protectionYes
Temperature protectionYes
Strings monitoringYes
I/V Curve scanningYes
Integrated PID recoveryOptional
Integrated AFCI (DC arc-fault circuit protection)Yes
Integrated DC switchOptional
General Data
Dimensions (W*H*D)647*629*252 mm
Weight37 kg
TopologyTransformerless
Self-consumption (night)<1 W
Operating ambient temperature range-25 ~ +60°C
Relative humidity0-100%
Ingress protectionIP66
Cooling conceptIntelligent redundant fan-cooling
Max. operation altitude4000 m
Grid connection standardG99, VDE-AR-N 4105 / VDE V 0124, EN 50549-1, VDE 0126 / UTE C 15 / VFR:2019, RD 1699 / RD 244 / UNE 206006 / UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1, EIFS 2018.2, IEC 62116, IEC 61727, IEC60068, IEC 61683, EN 50530
Safety/EMC standardIEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4
Features
DC connectionMC4 connector
AC connectionOT terminal
DisplayLCD
CommunicationRS485, Optional: Wi-Fi, GPRS