The JEBEL 12K heat pump monoblock R290 (AC only, no solar) is an advanced heating and cooling system in a single compact unit, providing space heating (underfloor, radiators, fan coils), cooling and domestic hot water for homes and businesses, with eco-friendly R290 refrigerant and A+++ seasonal heating efficiency.
Technical Specifications
| Model | JBL-HP-12K-HYB-R290P3 | JBL-HP-16K-HYB-R290P3 |
| Power Supply | ||
| Power AC (V/Ph/Hz) | AC380-415V/3Ph/50/60Hz | |
| Cooling (A35W18) | ||
| Capacity (kW) | 12.0 | 16.0 |
| Rated Input (kW) | 2.67 | 4.10 |
| EER | 4.5 | 3.9 |
| Cooling (A35W7) | ||
| Capacity (kW) | 11.5 | 14.0 |
| Rated Input (kW) | 3.77 | 5.09 |
| EER | 3.05 | 2.75 |
| Heating (A7W35) | ||
| Capacity (kW) | 12.0 | 15.0 |
| Rated Input (kW) | 2.50 | 3.41 |
| COP | 4.8 | 4.4 |
| Heating (A7W45) | ||
| Capacity (kW) | 12.0 | 15.0 |
| Rated Input (kW) | 3.24 | 4.48 |
| COP | 3.7 | 3.35 |
| Heating (A7W55) | ||
| Capacity (kW) | 12.0 | 15.0 |
| Rated Input (kW) | 3.87 | 5.26 |
| COP | 3.1 | 2.85 |
| Efficiency | ||
| Seasonal space heating energy efficiency class (LWT 35 °C) | A+++ | |
| Seasonal space heating energy efficiency class (LWT 55 °C) | A++ | |
| SCOP (LWT 35 °C) | 4.99 | 4.83 |
| SCOP (LWT 55 °C) | 3.91 | 3.76 |
| ErP sound power level (dB) | 57 | 58 |
| Max power input (kW) | 4.8 | 5.9 |
| Max current AC (A) | 9.5 | 11.5 |
| Components | ||
| Refrigerant type/GWP | R290/3 | |
| Refrigerant charged volume (kg) | 1.43 | |
| Compressor | Rotary – PANASONIC | |
| Water pump | DC high-efficiency shielded pump – SHIMGE/Shinhoo | |
| Max. pump head (m) | 9 | |
| Outdoor fan | DC brushless motor, horizontal, 250 W | |
| Water side heat exchanger | Brazed plate | |
| Air side heat exchanger | Finned tube | |
| Throttle type | Electronic expansion valve | |
| Water Circuit | ||
| Piping connections (inch) | G1-1/4" | |
| Safety valve set pressure (MPa) | 0.3 | |
| Flow switch (m³/h) | 0.60 | |
| Expansion tank volume (L) | 5 | |
| Back-up heater capacity (kW) | 9 | |
| Operating Range | ||
| Ambient temp. – cooling (°C) | -5 ~ 48 | |
| Ambient temp. – heating (°C) | -25 ~ 35 | |
| Ambient temp. – DHW (°C) | -25 ~ 43 | |
| Water temp. – cooling (°C) | 10 ~ 30 (LWT 5 ~ 25) | |
| Water temp. – heating (°C) | 25 ~ 80 | |
| Water temp. – DHW (°C) | 25 ~ 75 | |
| Dimensions | ||
| Net dimension W×D×H (mm) | 1283×455×1036 | |
| Packing dimension W×D×H (mm) | 1360×545×1222 | |
| Net weight (kg) | 175 | |
| Gross weight (kg) | 199 | |