The Huawei JUPITER-6000K-H1 Smart Transformer Station is a prefabricated, pre-tested solution in a compact 20' HC container with no internal cabling needed on site. Its high-efficiency transformer and low self-consumption raise yields, while real-time detection of the transformer, LV panel and RMU with remote control of ACB and MV breaker ensure smart, reliable operation.

Technical Specifications

ModelJUPITER-9000K-H1JUPITER-6000K-H1JUPITER-3000K-H1
Input
Available Inverters / PCSSUN2000-330KTL-H1 / SUN2000-330KTL-H2 / LUNA2000-200KTL-H1
Max. LV AC Inputs302211
AC Power9,000 kVA @40 ° C6,600 kVA @40 ° C3,300 kVA @40 ° C
Rated Input Voltage800 V
LV Panel SegregationForm 2b
LV Main SwitchesACB (4,000 A, 2 x 1 pcs)ACB (2,900 A, 2 x 1 pcs)ACB (2,900 A, 1 x 1 pcs)
LV Main Switches for Inverters / PCSMCCB (400 A, 2 x 15 pcs)MCCB (400 A, 2 x 11 pcs)MCCB (400 A, 11 pcs)
Output
Rated Output Voltage10~35 kV
Frequency50 Hz or 60 Hz
Transformer TypeOil-immersed, Conservator Type
Transformer Cooling TypeONAN
Transformer Tappings± 2 x 2.5%
Transformer Oil TypeMineral Oil (PCB Free)
Transformer Vector GroupDy11-y11Dy11
Transformer Min. Peak Efficiency IndexTier 1 or Tier 2 In Accordance with EN 50588-1
RMU TypeSF 6 Gas Insulated
RMU Transformer Protection UnitMV Vacuum Circuit Breaker Unit
Auxiliary TransformerDry Type Transformer, 5 kVA, Single-phase
Output Voltage of Auxiliary Transformer230 / 127 Vac
Protection
Transformer Detection & ProtectionOil Level, Oil Temperature, Oil Pressure and Buchholz
Protection Degree of MV & LV RoomIP 54
Internal Arcing Fault of STSIAC A 20 kA 1s
MV Relay Protection50/51, 50N/51N
LV Overvoltage ProtectionType I+II
Anti-rodent ProtectionC5-Medium
General
Dimensions (W x H x D)6,058 x 2,896 x 2,438 mm (20' HC ISO Container)
Weight< 28 t< 23 t< 15 t
Operating Temperature Range-25 ° C ~ 60 ° C
Relative Humidity0% ~ 95% (Non-condensing)
Max. Operating Altitude1,000 m
CommunicationModbus TCP, Preconfigured with SmartACU2000D
Standards ComplianceIEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1