مرجع داخلي:
JBL-PCS-100
The JEBEL 100kW Power Conversion System (PCS) is a bidirectional battery inverter for C&I and utility-scale energy storage, rated 100 kW at 400V AC.
Technical Specifications
| Model | JBL-PCS-100 | JBL-PCS-250 | JBL-PCS-500 | JBL-PCS-630 | JBL-PCS-1000 |
| AC (on-grid) | |||||
| Apparent power | 110kVA | 275kVA | 550kVA | 693kVA | 1000kVA |
| Rated power | 100kW | 250kW | 500kW | 630kW | 1000kW |
| Rated voltage | 400V | ||||
| Rated current | 144A | 361A | 722A | 909A | 1443A |
| Voltage range | 360V-440V | ||||
| Rated frequency | 50/60Hz | ||||
| Frequency range | 45~55/55~65Hz | ||||
| THDi | <3% | ||||
| PF | 0.8 lagging~0.8 leading | ||||
| AC connection | 3/N/PE | 3/PE | |||
| Max. rectified power | 100kW | 250kW | 500kW | 630kW | 750kW |
| AC (off-grid) | |||||
| Apparent power | 110kVA | 275kVA | 550kVA | 693kVA | 1000kVA |
| Rated power | 100kW | 250kW | 500kW | 630kW | 1000kW |
| Rated current | 144A | 361A | 722A | 909A | 1443A |
| THDu | ≤2% linear | ||||
| Overload capability | 110%-10 mins 120%-1 min | ||||
| DC (Battery) | |||||
| Rated power | 100kW | 250kW | 500kW | 630kW | 1000kW |
| Current / voltage regulation | ±1% | ||||
| Voltage ripple / current ripple | <3% / <2% | ||||
| Voltage range | 500V-820V | 500V-820V | 600V-900V | 600V-900V | 650V-900V |
| Max. charge/discharge current | 220A | 550A | 917A | 1155A | 1154A/1600A |
| General Information | |||||
| Max. efficiency | 97.10% | 97.30% | 98.50% | 98.50% | 99.0% |
| Dimension (W/H/D) mm | 1100/1890/850 | 1600/2080/850 | 1200/1900/800 | 1200/1900/800 | 1510/1900/850 |
| Weight | 820kg | 1465kg | 870kg | 900kg | 1500kg |
| Built-in transformer | Yes | No | |||
| Lightning protection | Type II | ||||
| Protection degree | IP20 | ||||
| Noise emission | <75dB(A)@1m | ||||
| Operating temperature | -25°C~+55°C | ||||
| Cooling method | Forced-air | ||||
| Relative humidity | 0-95% non-condensing | ||||
| Max. altitude | 6000m (derate above 3000m) | ||||
| Transfer between on/off grid | Manual (default), Automatic (optional) ≤ 10ms | ||||
| Grid support | L/HVRT, FRT, active & reactive power control and power ramp rate control. Volt-var, Volt-watt. Frequency-watt | ||||
| Display | Touch screen | ||||
| Communication | RS485/CAN | ||||