Technical Specifications

ModelACR10RH-DxxT(R)E4
Technical Parameters
Network3-phase 3-wire, 3-phase 4-wire
Frequency45-65Hz
Rated voltageAC 57.7V/100V(100V), 220V/380V(400V)
Voltage overload1.2-fold rating (continuous); 2-fold rating/1 second
Rated current80A, 120A, 200A etc. (see specific product specifications)
Current overload1.2-fold rating (continuous); 10-fold rating/1 second
Consumption<0.2VA
Energy pulse outputOpen-collector photocoupler pulse, two way output; pulse constant 4000/8000imp/kWh
CommunicationRS485 interface, Modbus-RTU Protocol
Display modeLCD
Switching input / outputFour way dry contact input; two way relay NO contact output (AC 250V/3A, DC 30V/3A)
Measuring accuracyFrequency 0.05Hz, reactive electric energy class 1, other class 0.5
Power supplyAC85-265V or DC100-350V, DC24V ±10%, DC48V ±10%; consumption ≤10VA
Insulation resistanceInput, output terminal to housing >100MΩ
Working temperature-10 ~ +55°C
Storage temperature-20 ~ +70°C
Relative humidity5% ~ 95% no condensation
Altitude≤2500m
Functions
Current/voltage/frequency/power factorStandard
Active/reactive/apparent powerStandard
Four quadrant electric energy measurementStandard
Total harmonic content / 2-31 subharmonicsStandard
RS485 interfaceStandard
Maximum demand, multi-rate energy, incident record, alarm, built-in clockOptional
InstallationGuide rail (DIN rail)